WSG30 Users Manual
36
Power suPPly wIrIng
To connect the power supply, remove the sensor cover and locate the screw terminals labeled “5V DC”.
connect the positive wire from the power supply to the “+” terminal. Plug the power supply into an
appropriate outlet.
1.375”
MountIng
The sensor can be mounted directly on a flat surface. Consideration should
be given as to whether or not an electrical outlet will be required if using the
optional power supply. Mount the sensor as high as possible to provide for
optimal Wireless transmission. When installed within a building where the
Wireless signal must travel through several obstructions, the sensor should
be located within 250’ of the WSG30 or within 300’ of a sensor/router.
Use a pencil to mark the hole locations at the top and bottom of the housing.
Install the drywall anchors (if necessary) to the wall. Attach the housing to
the wall using #6 tapping screws.
sPeCIFICatIons
Operating Temperature Range: 32° to 122°F (0° to 50° C)
Operating Humidity: 5- 90% RH non-condensing
Range (Indoor/Urban): Up to 300’ (90m)
Transmit Power Output: 100mW (20dBm)
Operating Frequency: ISM 2.4 GHz
Power: (2) AA alkaline batteries and 5VDC (300mA) plug-in adapter
Battery Life: Up to 2 years @ sampling interval = 3 seconds (with power off)
Dimensions: 3.1” x 3.8” x 1.1” (7.9cm x 9.8cm x 2.85cm)
Housing: White plastic
*Specifications subject to change without notice