beautypg.com

Appendix a: weekly testing procedure – Sensaphone WSG30 System Users manual User Manual

Page 46

background image

WSG30 Users Manual

46

AppENdix A: WEEkLY

tEStiNg pRoCEdURE

We recommend that you test your WSG30 system weekly to be sure it is functioning properly. This will

ensure that when a problem arises the WSG30 will be ready to alert the appropriate personnel. A test log

template is included at the back of this manual.

There are several tests that can be performed:

1) Check the status of all monitored conditions on the WSG30 by viewing the web page. This will verify

that the WSG30 and sensors are communicating and that all of the inputs are reading properly. In

addition, you can verify that the electricity is on and that the backup battery is OK.

2) Create an alarm on each Wireless sensor.

Temperature sensors: Heat or cool the sensor.

Humidity sensors: Raise the humidity around the sensor by holding a cup of very hot water

beneath the sensor.

Dry Contact sensors: Open or close the circuit to create an alarm condition.

Water sensors: Apply a small amount of water beneath the sensor or use a wet towel and

touch it to the sensor probes and/or sensing rope.

Power Sensor: Disconnect the sensor power supply from the wall outlet.

Allow the unit to send its alarm message to all programmed contacts. This will make

sure that the WSG30 is programmed properly. It will also prepare personnel to respond

appropriately when they receive a message from the unit.

3) Test the batteries in the WSG30 and each Sensor by unplugging the power supply and making sure

that the device and all of its sensors continue to function.

4) If you require assistance, call Sensaphone Technical Support at (610)558-2700.