beautypg.com

Sensaphone WSG30 System Users manual User Manual

Page 40

background image

WSG30 Users Manual

40

soFtware ConFIguratIon
The Wireless 4-20mA sensor can provide a scaled value to match the calibrated range of your

transducer. In the WSG30 web page, open the Sensor Edit screen for the Wireless 4-20mA Bridge

sensor. Insert the Low (4mA) and High (20mA) values for your transducer into the Table Low and Table

High fields. The WSG30 will display the scaled value. You may wish to include the units of measure in

the Units field.

sPeCIFICatIons
Operating Temperature Range: 32° to 122°F (0° to 50°C)
Operating Humidity: 5- 90% RH non-condensing
Battery Life (24VDC Supply enabled): 15 hours
Battery Life (24VDC Supply disabled): 2 years @ sampling interval = 3 seconds
Input Load: 260 Ohms
Accuracy: ± 1%
Absolute Max Input Current: 23mA
Range (Indoor/Urban): Up to 300’ (90m)
Transmit Power Output: 100mW (20dBm)
Operating Frequency: ISM 2.4 GHz
Power: (3) AA alkaline batteries and/or 5VDC (300mA) plug-in adapter
Dimensions: 6.8” x 3.5” x 1.5”
Housing: White plastic

*Specifications subject to change without notice