Robustel GoRugged R3000 User Guide
RT_UG_R3000_v.2.0.0 17.01.2014 55 / 131
Confidential
DO @ DI/DO
Item
Description
Default
Enable
Click to enable DO.
Disable
Alarm Source
Digital Output initiates according to different alarm source.
Selected from “DI Alarm”, “SMS Control”, “Call Control”, selections can be one or
more.
DI Alarm: Digital Output triggers the related action when there is alarm from Digital
Input.
SMS Control: Digital Output triggers the related action when receiving SMS from
the number in the phone book.
Call Control: Digital Output triggers the related action when receiving phone call
from the number in the phone book.
Null
Alarm On Action
Digital Output initiates when there is an alarm.
Selected from “OFF”, “ON”, “Pulse”.
OFF: Open from GND when triggered.
ON: Short contact with GND when triggered.
Pulse: Generates a square wave as specified in the pulse mode parameters when
triggered.
ON
Alarm Off Action
Digital Output initiates when alarm recovered.
Selected from “OFF”, “ON”, “Pulse”.
OFF: Open from GND when triggered.
ON: Short contact with GND when triggered.
Pulse: Generates a square wave as specified in the pulse mode parameters when
triggered.
ON
Status When Power
On
Specify the Digital Output status when power on.
Selected from “OFF”, “ON”.
OFF: Open from GND.
ON: Short contact with GND.
ON
Keep On (s)
Available when digital output Alarm On Action/Alarm Off Action status is ON, input
the Digital Output keep on status time.
Input from 0 to 255 seconds. (0=keep on until the next action)
0