Robustel R3000 User Guide User Manual
Page 53
Robustel GoRugged R3000 User Guide
RT_UG_R3000_v.2.0.0 17.01.2014 52 / 131
Confidential
Note: when you do not enable any VPN tunnel, this item will not show up.
Interval
Timeout
@Transparent
The serial port will queue the data in the buffer and send the data to the
Cellular WAN/Ethernet WAN when it reaches the Interval Timeout in the
field.
Note: Data will also be sent as specified by the packet length or delimiter
settings even when data is not reaching the interval timeout in the field.
10
Packet
Length
@Transparent
The Packet length setting refers to the maximum amount of data that is
allowed to accumulate in the serial port buffer before sending. 0 for packet
length, no maximum amount is specified and data in the buffer will be sent
as specified by the interval timeout or delimiter settings or when the buffer
is full. When a packet length between 1 and 1024 bytes is specified, data in
the buffer will be sent as soon it reaches the specified length.
Note: Data will also be sent as specified by the interval timeout or delimiter
settings even when data is not reaching the preset packet length.
1360
Enable Delimiter1
When Delimiter 1 is enabled, the serial port will queue the data in the buffer
and send the data to the Cellular WAN/Ethernet WAN when a specific
character, entered in hex format, is received. A second delimiter character
may be enabled and specified in the Delimiter 2 field, so that both
characters act as the delimiter to control when data should be sent.
Disable
Delimiter1 (Hex) @
Transparent
Enter the delimiter in Hex.
0
Delimiter Process @
Transparent
The Delimiter process field determines how the data is handled when a
delimiter is received.
None: Data in the buffer will be transmitted when the delimiter is received;
the data also includes the delimiter characters.
Strip: Data in the buffer is first stripped of the delimiter before being
transmitted.
Strip
Local IP @ Modbus
This item will show up When you enable any VPN tunnel of R3000, it means
serial data can be matched to this local IP address and be transmitted or
received via VPN tunnel.
Note: when you do not enable any VPN tunnel, this item will not show up.
0
Local Port @ Modbus
Enter the Local port for Modbus.
0
Attached serial device
type @ Modbus
Select From “Modbus RTU slave”, “Modbus ASCⅡ slave”, “Modbus RTU
master” and “Modbus ASCⅡ master”.
Modbus RTU slave: router connects to slave device which works under
Modbus RTU protocol.
Modbus ASCⅡ slave: router connects to slave device which works under
Modbus ASCⅡprotocol.
Modbus RTU master: router connects to master device which works under
Modbus RTU protocol.
Modbus ASCⅡ master: router connects to master device which works
under Modbus ASCⅡ protocol.
Modbus
RTU slave
Modbus
Slave
@ Add the Modbus slaves which will be polled by Modbus master (router). This Null