beautypg.com

1 transformer wiring, 4 . 2 . 1 transformer wiring – MTS Model 506-62-72 Hydraulic Power Supply User Manual

Page 32

background image

4-4 Installation

4 . 2 . 1

Transformer Wiring

One of two types of transformers is installed in the starter assembly.
Check the wiring configuration of the transformer before applying ac
power to the HPS.

Standard transformer
wiring

This figure shows the jumper wiring required on a standard transformer
for source voltages of 460 and 230 Vac.

jumper

H1

X2

H2

X1

H3

460 Vac

H4

H1

X2

H2

X1

H3

230 Vac

H4

VW-C036

jumper

jumper

Figure 4-4. Standard Transformer Wiring Configuration

Optional transformer
wiring

An optional multi-tap transformer may be used for source voltages other
than 230 Vac and 460 Vac. The following figure shows the typical
wiring required for various voltages. Source voltages are applied to
terminals H1 through H5 as shown. An output voltage is tapped from
terminals X1 through X4. Check the output voltage with a voltmeter.
It should be 110 Vac for systems using 50 Hz power and 115 to 120 Vac for
systems with 60 Hz.

X4

VW-C037

X3

X2

X1

H4

H5

H3

H2

H1

208/220/230/240 Vac

380/400/416 Vac

440/460/480 Vac

500/550/575/600 Vac

110/120/125/130 Vac

100/110/115/120 Vac

85/91/99 Vac

Figure 4-5. Typical Multi-Tap Transformer Wiring Configuration