8 control of the sequence table, Control of the sequence table ( 43) – Lenze E94AxHE Technology Application Positioning sequence control User Manual
Page 43
EDS94TA10060xxxx EN 1.2 - 03/2010
L
43
9400 Technology applications | Positioning sequence control
Parameter setting & configuration
Program flow
5.3.8
Control of the sequence table
A LOW/HIGH edge at the digital input DI6 starts the parameterised program flow if the
controller is enabled and no error is pending.
The first step set in C03000 of the sequence table is executed.
By setting the digital input DI7 to HIGH level, the program flow can be stopped, if
required (break).
Parameter setting: Tab Application parameters dialog level Overview L_Sequencer
Note!
In the following cases the program flow is interrupted:
• The controller inhibit is activated.
• Quick stop is activated.
• The drive interface changes to an error status.
If the controller is not inhibited, a shutdown of the drive via the basic function
"Quick stop" is effected.
After the interruption is deactivated again (e.g. because an activated quick stop
has been deactivated again), a renewed LOW/HIGH edge is required at the
digital input DI6 in order that the positioning program can be continued with
the sequence step.
Parameter
Lenze setting
Value Unit
C03000
First step
1
C04504
Jump destination
0
Control inputs of the function
Signal configuration
Lenze setting
Control input
(Multiplexer parameters)
C03000 First step
C03079/6
DIGIN 6 Sequencer start
C03070/1
DIGIN 7 Sequencer break
C03070/2
FALSE Sequencer jump
C03070/3
FALSE Sequencer abort
C03070/4
FALSE Sequencer interruption
C03070/5
Controller inhibit
or
Quick stop active
or
Error active
Reset program status
C03070/6
DIGIN 5 Reset program/error status
C03070/8