2 action type "homing, Action type "homing" ( 36), Parameter setting & configuration program flow – Lenze E94AxHE Technology Application Positioning sequence control User Manual
Page 36

9400 Technology applications | Positioning sequence control
Parameter setting & configuration
Program flow
36
L
EDS94TA10060xxxx EN 1.2 - 03/2010
5.3.2
Action type "Homing"
In order to execute a homing process, the action type "Homing" is available for the
sequence table which activates the basic function "Homing".
[5-3]
"Homing" (schematic diagram for limited traversing range)
Parameter setting: Tab Application parameters dialog level Overview Homing
Basic drive functions
0
-100
100 200
LS_Homing
DI2
Sequencer
Enable/activate
homing
Status
machine
(basic drive
functions)
M
State "homing done"
DI7
DI6
DI5
Reset
Sequencer
input 8
DI8
Positioning sequence control
Note!
The "Homing" action for the sequence table does not have its own parameters.
The settings for homing are made via the parameters of the basic function
"Homing".
Parameter
Lenze setting
Value Unit
C02528
Traversing range
Limited
C02640
Homing mode
Set home pos. directly
C02642
Home position
0.0000 unit
C02643
Homing: Target position
0.0000 unit
C02644
Homing: Speed 1
360.0000 unit/s
C02645
Homing: Acceleration 1
720.0000 unit/s
2
C02646
Homing: Speed 2
180.0000 unit/s
C02647
Homing: Acceleration 2
360.0000 unit/s
2
C02648
Homing: S-ramp time
100 ms
C02649
Homing: Torque limit
10.00 %
C02650
Homing: Blocking time
1.000 s
C02652
Ref. pos. after mains switching
Delete
C02653
Max. rot. ang. aft. mns. swtch.
180 °