Parameter menu – Lenze MC1000 Series User Manual
Page 47

13435742_EDBM101_v24
43
PARAMETER MENU
PARAM.
NUMBER
PARAMETER
NAME
RANGE OF
ADJUSTMENT
FACTORY
DEFAULT
52
53
54
TB14 OUT
TB15 OUT
RELAY
NONE, RUN, FAULT, /FAULT,
LOCK, @ SPEED, ABOVE #3,
I LIMIT, AUT/MAN, FLWR PR, MIN/
MAX ALARM,
INV MIN/MAX A,
MIN ALARM, INV MIN ALARM,
MAX ALARM, INV MAX ALARM,
REVERSE, SLEEP, SPD = 0HZ
NONE
55
TB5B LOSS
FAULT, SP#4, NONE
FAULT
57
SERIAL
DISABLED, W/TIMER, W/O TIMR
DISABLE
58
ADDRESS
1 - 247
30
61
PASSWORD
0000 - 9999
0019
63
SOFTWARE
(VIEW - ONLY)
(N/A)
64
MONITOR
OFF, ON
ON
65
PROGRAM
MAINTAIN, RESET 60,
RESET 50 (NOTE 4)
RESET 60
66
HISTORY
MAINTAIN, CLEAR
MAINTAIN
70
PID MODE
OFF, NORMAL, REVERSE
OFF
74
PID FB
TB-5A, TB-5B
TB-5A
75
FB @ MIN
-32768 to 32767
0.0 %
76
FB @ MAX
-32768 to 32767
100.00 %
77
P GAIN
0.0 - 999.9 %
5.0 %
78
I GAIN
0.0 - 10.0 SEC
0.0 SEC
79
D GAIN
0.0 - 10.0 SEC
0.0 SEC
80
PID ACC
0.0 - 100.0 SEC
30.0 SEC
81
MIN ALRM
FB @ MIN - FB @ MAX
0.0 %
82
MAX ALRM
FB @ MIN - FB @ MAX
0.0 %
98
LANGUAGE
ENGLISH
99
FAULT HISTORY
(VIEW - ONLY)
(N/A)
NOTE 4:
"RST HIGH" WILL APPEAR ON UNITS SET UP FOR HIGH FREQUENCY.
NOTE!
If you are working with Software M108313 or ealier (see Parameter 63),
parameters 69 and 70 are shown here as parameters 98 and 99.