7 Object dictionary
0x2002 -
UINT16 RW
1
EMCY_Time
Time for cyclic trans-
mission of error
messages
0 — 65535 msec
0 = once
ex-fact. 1000 msec
0x3100 0x01
float
RO
Al PV Min 1
Drag pointer
minimum value
0x02
float
RO
Al PV Min 2
as subindex 0x01, for
devices with 2 sensors
0x3101 0x01
float
RO
Al PV Max 1
Drag pointer
maximum value
0x02
float
RO
Al PV Max 2
as subindex 0x01, for
devices with 2 sensors
0x3102 0x01
UINT32 WO
Al Reset Min-
Max 1
Reset drag pointers
0x3100 and 0x3101
Reset with "roeb" =
0x62656F72
0x02
UINT32 WO
Al Reset Min-
Max 2
as subindex 0x01, for
devices with 2 sensors
0x3400 -
String
(4)
RW
Al Customer
Date
any text,
4 bytes,
e.g. date
ex-factory: "0003"
0x3401 -
String
(4)
RW
Al Customer
Name
any text,
4 bytes,
e.g. name
ex-factory: "ROEB"
0x6124 0x01
float
RW
Al Offset 1
Customer fine
calibration
ex-factory: 0
0x02
float
RW
Al Offset 2
as subindex 0x01, for
devices with 2 sensors
0x6125 0x01
UINT32 WO
Al Autozero
With pressure sensors
only:
show current pressure
as zero, alters object
0x6124,1
Set to zero with
“zero” =
0x6F72657A
0x6126 0x01
float
RW
Al Scaling
Factor 1
Scaling of factor
ex-factory: 1
e.g. 0.1, to show
pressure not as
0 — 100% but as
0 — 10 bar; or e.g.
1.8, to show tempe-
rature not in °C but
in °F.
0x02
float
RW
Al Scaling
Factor 2
as subindex 0x01, for
devices with 2 sensors