5 CANopen function
5.3
Sync
The PDOs of the CANtrans transmitter can be configured as “synchronous”.
When a Sync object has been received, the corresponding PDO will be trans-
mitted.
Settings for
Sync
The PDO transmission type can be switched between synchronous (controlled
by the master) and asynchronous (event-controlled) in the object dictionary
(0x1800,2 or 0x1804,2).
Factory setting: event-controlled (=0xFF)
5.4
Emergency
In the event of a sensor short-circuit or sensor break, the CANtrans transmit-
ters will send a high-priority emergency object (EMCY).
The telegram will be repeated cyclically. The cycle time can be set.
EMCY user
data (8 bytes)
Transmission type
Setting the object
0x1800,2 (for PDO1)
0x1804,2 (for PDO5)
event-controlled
0xFF
synchronous
0x01
Sensor break
Byte 1
Byte 2
Byte 3
Byte 4
Byte 5
Byte 6
Byte 7
Byte 8
5030 h
(hardware)
2 bytes
00000001
1 byte
1 or 2
(chann.)
1 byte
00000001
1 byte
not used
Sensor
short-circuit
Byte 1
Byte 2
Byte 3
Byte 4
Byte 5
Byte 6
Byte 7
Byte 8
5030 h
(hardware)
2 bytes
00000001
1 byte
1 or 2
(chann.)
1 byte
00000010
1 byte
not used
Reset error
Byte 1
Byte 2
Byte 3
Byte 4
Byte 5
Byte 6
Byte 7
Byte 8
0000 h
(hardware)
2 bytes
00000000
1 byte
1 or 2
(chann.)
1 byte
xxxxxxxx
1 byte
not used