3 Installation

3.1

Electrical connection

Bus cable

- the bus specifications to ISO 11 898 must be observed

- cable diameter 6 to 12 mm

- conductor cross-section up to 1.5mm

2

per core

- signal cables must be routed separately from cables with voltages

above

60 V

- use cables with twisted cores

- avoid the vicinity of electrical installations, or use screened cables

Connection

Circular
connector

M12 x1; 5-pole to IEC 60 947-5-2

Earth the instrument at the pressure connection.
The bus ends must be provided with a line termination.
➩ Chapter 3 “Installation” / “Line termination”, page 11.

Connection

Terminal assignment

M12
connector

terminal box with
moulded cable

Sales No.
40/00337625

Supply voltage
10 — 30 V DC

CAN_V+
CAN_GND

2
3

white
blue

Output
CANopen

screen
CAN_H
CAN_L

1
4
5

brown
black
gray

1

5

4

2

3

2

5

3

1

4

Plug

Socket