17

5 CANopen function

Setting for
Emergency

Factory setting: once per second (= 1000 msec)

5.5

PDO

1 or 2 transmit PDO(s) (process data object) are available for the measure-
ments.

The setting for mapping (0x1A00) of the PDO user data is fixed to 0x9130
(measurement in fixed-point format) and to 0x6150 (status byte).
The calculation of these values is described in see chapter 6 “Device
function”, page 23.

Status bit 0 = Sensor faulty (sensor monitoring)

Status bit 1 = overrange (measurement range monitoring)
Status bit 2 = underrange (measurement range monitoring)

EMCY time

Setting the object
0x2002

milliseconds

0 — 65535 (0 = not repeated)

PDO
user data
(5 bytes)

Byte 1

Byte 2

Byte 3

Byte 4

Byte 5

Byte 6

Byte 7

Byte 8

0x9130

4 bytes

measurement INT32

0x6150

1 byte

status

bit 2, 1, 0

not used

not included in transmission

If bit 0 is set, the measurement transmitted in the PDO is
invalid!