beautypg.com

8 overcoming errors and malfunctions, 1 possible errors, Overcoming errors and malfunctions – JUMO 902940 DELOS T Electronic Temperature Switch with Display and Analog Output Operating Manual User Manual

Page 69: Possible errors

background image

69

8 Overcoming errors and malfunctions

8.1

Possible errors

Display

Possible causes

Measure

Overrange
or underrange

Probe break

Check temperature and/or probe.

Device error

1 = Internal
communication error

2 = Error, analog output

3 = Short circuit,
switching output 1

4 = Short circuit,
switching output 2

5 = VCC 8 V outside the
working range

6 ... 8 = Internal
communication error

9 = Invalid configuration

1, 6, 7, 8: Contact the service.
2: Check ambient temperature.
Check output for cable break. Output
load too high (for current output) or
too low (for voltage output).
3, 4: Check the switching output.
5: Check voltage supply.
9: Check the configuration.

Display overrun:
Upper display: „- - - -“
Bottom display: Parameter name
Value is smaller than -9999
or exceeds +9999.

Check switching output.
Check voltage supply.