beautypg.com

6 commissioning/start-up – JUMO 902940 DELOS T Electronic Temperature Switch with Display and Analog Output Operating Manual User Manual

Page 53

background image

53

6 Commissioning/start-up

6.10

Setting the error signal of the analog output (S.Err)

In the event of errors (e.g. probe break or probe short-circuit), the analog output transmits the
signal configured here.

How to proceed:

Setting:

TIP!
An error signal for overrange or underrange is only transmitted on devices with analog output.

Step

Activity

1

Unlock the device.

Chapter 6.2 "Unlocking the device (enter the code).", page 42

2

"Turn" until "S.Err" appears in the bottom line.

3

"Press"

Type of signal

Setting

4 to20 mA

= 3.4 mA

= 22 mA

0 to 20 mA

= 0 mA

= 22 mA

0 to 10 V

= 0 V

= 10.7 V