11 behavior when the scaling range is exceeded, Behavior when the scaling range is exceeded, 6 commissioning/start-up – JUMO 902940 DELOS T Electronic Temperature Switch with Display and Analog Output Operating Manual User Manual

Page 54

background image

6 Commissioning/start-up

54

6.11

Behavior when the scaling range is exceeded

The standard signal range of the analog output is limited as per recommendation of Namur NE
43.

Example:
4 to 20 mA (factory setting)

Type of signal

lower limit

upper limit

4 to 20 mA

3.8 mA

20.5 mA

0 to 20 mA

0 mA

20.5 mA

0 to 10 V

0 V

10.2 V