6 Commissioning/start-up

64

6.18

Setting the display unit (D.Uni)

How to proceed:

Example:
The device scaling range was set to 0 to 150 °C.
When the device measures a temperature of 75 °C, 50 % is displayed.

Setting range:

Uni.t = Temperature unit set as for "Uni.T"

Chapter 6.4 "Setting the unit of the measured value (Uni.T)", page 44

Pro2 = Percent of the scaled measuring range = "Sc.Hi" minus "Sc.Lo"

Chapter 6.9.1 "Setting the scaling start value (Sc.Lo)", page 51

and

Chapter 6.9.2 "Setting the scaling end value (Sc.Hi)", page 52

Factory-setting:

Uni.t

Step

Activity

1

Unlock the device.

Chapter 6.2 "Unlocking the device (enter the code).", page 42

2

"Turn" until "D.Uni" appears in the bottom line.

3

"Press"

Uni.t = The measured value is displayed in the selected unit.

Chapter 6.4 "Setting the unit of the measured value (Uni.T)", page 44

or

Pro2 = The measured value is displayed in percent of the scaling range.

Chapter 6.9.1 "Setting the scaling start value (Sc.Lo)", page 51

and

Chapter 6.9.2 "Setting the scaling end value (Sc.Hi)", page 52