6 Commissioning/start-up

Customer specific scaling

It is frequently desired that a part of the measuring range is scaled to the output signal.
Example:
Actual
The device has a measuring range (1) from -50 to +150 °C and the output signal 4 to 20 mA
(3).
Set point
The customer wants that the "Customer scaling range“ (2) 0 to 50 °C (25 % from the measuring
range (1)) complies with the 4 to 20 mA (100 %) output signal.
Scaling is 1 : 4 (25 % : 100 %).

(1)

Measuring range

(2)

Customer scaling range

(3)

Output signal