9 Appendix

68

9.1.3

Electrical data

9.1.4

Case and ambient conditions

9.1.5

Approval/approval marks

Voltage supply

Connection

Lateral (feed via base unit or router module)

Voltage

DC 24 V +25/-20 %

Residual ripple

5 %

Current consumption

130 mA (at DC 19.2 V)

Power consumption

3 W

Inputs (terminals 1 to 18)

Connection

At the front (removable terminal strips with Push-In technology)

Conductor cross section on terminals 1 to 18

Wire or strand without ferrule

Min. 0.14 mm

2

, max. 1.5 mm

2

Strand with ferrule

Without plastic collar: Min. 0.25 mm

2

, max. 1.5 mm

2

With plastic collar: Min. 0.25 mm

2

, max. 0.5 mm

2

Stripping length on terminals 1 to 18

9 mm

Electrical safety

Acc. to DIN EN 61010-1
Overvoltage category III, pollution degree 2

Electromagnetic compatibility

Acc. to DIN EN 61326-1

Interference emission

Class A – only for industrial use –

Interference immunity

Industrial requirements

Case type

Plastic case for DIN rail mounting in the control cabinet (indoor use);
DIN rail acc. to DIN EN 60715, 35 mm x 7.5 mm x 1 mm

Dimensions (W × H × D)

22.5 m × 103.6 m × 101.5 m (without connection elements)

Weight

Approx. 140 g

Protection rating

IP 20, acc. to DIN EN 60529

Ambient temperature range

-20 to +55 °C

Storage temperature range

-40 to +70 °C

Resistance to climatic conditions

Relative humidity

90 % annual average without condensation (cli-

matic class 3K3 acc. to DIN EN 60721-3-3 with extended tempera-
ture and humidity range)

Site altitude

Up to 2000 m above sea level

Mechanical ambient conditions

1

Classification acc. to DIN EN 60721-3-3, table 6, class 3M2

1

Test conditions are listed in the System Descripton B 705000.8.

Approval mark

Testing agency

Certificate/certifica-
tion number

Inspection basis

Valid for

c UL us

Underwriters Laborato-
ries

E201387

UL 61010-1 (3. Ed.),
CAN/CSA-22.2
No. 61010-1 (3. Ed.)

all types