beautypg.com

3 connection diagram, 1 display and connection elements, Connection diagram – JUMO 705020 mTRON T - Analog Input Module, 4-Ch. Operating Manual User Manual

Page 25: 4 electrical connection

background image

25

4 Electrical connection

4.3

Connection diagram

4.3.1

Display and connection elements

CAUTION!
At maximum load, the temperature may exceed 60 °C at the terminals.
As a result the insulation of the cable may be damaged.
The cable must be heat resistant up to at least 80 °C.

(1) Status displays (LED)

P = Voltage supply
S = Status
1 = Digital input
(LED is lit: Active)

(2) Analog input 1 to 3
(3) Voltage supply Out, DC 24 V
(4) Side system bus Out
(5) Analog input 4;

digital input

(6) Side system bus In
(7) Voltage supply In, DC 24 V

(1)

(2)
(3)

(4)

(5)

(7)

(6)