beautypg.com

3 digital input, Digital input, 6 configuration – JUMO 705020 mTRON T - Analog Input Module, 4-Ch. Operating Manual User Manual

Page 43

background image

43

6 Configuration

6.3

Digital input

In addition to the analog inputs the module provides a digital input.
The status of the digital input is indicated by a LED. The display corresponds to the output sig-
nal to the system bus.

Setup dialog

Parameter

Parameter

Selection/settings

Description

Mode: Delay

0 s to 65535 s

Delay time during change of input signal
from Low to High (or from High to Low in
the case of active inverting)

Inverting

Inversion of the input signal

Normal

Not inverted

Inverse

Inverted

TAG number

7 characters

Identification marking (documentation in
PLC)

Signal suppres-
sion

Digital selector (Inactive)

Chapter 6.1 "Digital selector", page
33

Signal (high-active) for suppression of
the input signal

Level at suppres-
sion

Output level during active signal suppression

No choice

Low level (0)

Active

High level (1)

Alarm type

The alarm type is not set by default.

CollectiveAlarm

Alarm results in collective alarm of the
module.

Event

Alarm results in an entry (event text) in
the event list.

Alarm active at

High (1)

Alarm at high level (1)

Low (0)

Alarm at low level (0)

?