9 Appendix
Standard signals
Measuring circuit monitoring
In the event of an error the digitized output values move to a defined status.
9.1.2
Digital input
Designation
Measuring range
Measuring accu-
racy
1
Ambient
temperature influ-
ence
Voltage
≤
0.05 %
100 ppm/K
Input resistance R
E
> 500 k
Ω
DC 0(2) to 10 V
Input resistance R
E
> 100 k
Ω
DC 0 to 1 V
Current (voltage drop
≤
2 V)
DC 0(4) to 20 mA
≤
0.05 %
100 ppm/K
Resistance transmitter
min. 100
Ω
,
max. 4 k
Ω
±
4
Ω
100 ppm/K
Resistance/potentiometer
<
400
Ω
400
Ω
to 4 k
Ω
±
0.4
Ω
±
4
Ω
50 ppm/K
50 ppm/K
1
The accuracy values refer to the maximum measuring range. Smaller measuring ranges lead to reduced lineariza-
tion accuracy.
Measuring element
Out of range
Probe/cable short
circuit
Probe/cable break
Thermocouple
Is detected
Is not detected
Is detected
RTD temperature probe
Is detected
Is detected
Is detected
Voltage
2 to 10 V
Is detected
Is detected
Is detected
0 to 10 V
Is detected
Is not detected
Is not detected
0 to 1 V
Is detected
Is not detected
Is not detected
Current
4 to 20 mA
Is detected
Is detected
Is detected
0 to 20 mA
Is detected
Is not detected
Is not detected
Resistance transmitter
Is detected Is
not
detected Is
detected
Resistance/potentiometer Is
detected Is
detected Is
detected
Number 1
Input signal
DC 0/24 V
(PLC level; logical “0” = -3 to +5 V; logical “1” = +15 to +30 V)