6 configuration, 1 digital selector, Configuration – JUMO 705020 mTRON T - Analog Input Module, 4-Ch. Operating Manual User Manual
Page 33: Digital selector
33
6 Configuration
6.1
Digital selector
The digital selector contains all digital signals that are available in the analog input module 4-
channel to configure the following functions.
•
Alarm suppression (see Chapter 6.2.1 "Alarms", page 39)
•
Signal suppression (see Chapter 6.3 "Digital input", page 43)
The following table lists all digital signals. The entry in the "Type" column indicates the source
of the signal:
•
Internal: Internal signal of the analog input module 4-channel (including the signal of the dig-
ital input)
The signal is also transmitted to the base unit via the system bus, to allow it to be used by
other modules.
•
External: External input (NV_...) that must be linked in the NV connecting list to a signal
from another module (see Chapter 6.4 "NV connecting list", page 45).
The signal name "NV_..." indicates the intended use; in principle, the signal can also be
used for other purposes.
Alarm
The collective alarm of the analog input module 4-channel is made up of all functions for which
the "Collective alarm" alarm type has been activated.
TIP!
The parameters described in this section can be configured either with the setup program or
on the multifunction panel.
Category
Signal
Type
Description
Inactive
No signal selected
Analog inputs
AI01Alarm1 to AI04Alarm1
Internal
Alarm signal 1 of analog input 1 to
4
AI01Alarm2 to AI04Alarm2
Internal
Alarm signal 2 of analog input 1 to
4
Digital inputs
DI01
Internal
Signal of digital input
Signal rejections
NV_SR01 to NV_SR05
External
Signal for activating signal sup-
pression
Alarm
CollectiveAlarm
Internal
Module collective alarm
?