6 configuration – JUMO 705020 mTRON T - Analog Input Module, 4-Ch. Operating Manual User Manual
Page 36
![background image](/manuals/563346/36/background.png)
6 Configuration
36
Linearization
Linearization must be selected according to the sensor (measuring probe).
The predefined linearizations can be supplemented with customer-specific linearization.
Chapter 7.1 "Customer-specific linearization", page 53
Scale start
Factory setting depends on sensor and linearization.
-99999 to +99999
Start value of display range
Scale end
Factory setting depends on sensor and linearization.
-99999 to +99999
End value of display range
TAG number
7 characters
Identification marking (documentation in
PLC)
Unit
5 characters (%)
Unit for numerical representation of
measured value
Offset type
Type of measured value offset
Standardized
Offset of standardized measured value
(after linearization)
Physical
Offset of physical measured value
(before linearization)
Offset
-100 to 0 to +100
Correction value
Filter time con-
stant
0 s to 0.6 s to 100 s
Time constant for adjusting the digital
input filter (0 s = filter off)
Cold junction
Selection of cold junction (for thermocouple)
Internal Pt100
Internal Pt100 temperature probe
External constant
Constant cold junction temperature
Ext. reference
temp.
-20 to 0 to +200
Cold junction temperatures (for thermo-
couple and constant cold junction tem-
perature)
Resistance Ra or
Ro
0 W to 4000
Ω
For Resistance transmitter:
Resistance Ra between sliding contact
(S) and start (A), if the sliding contact is
positioned at the start.
For Resistance/potentiometer:
Offset resistance Ro
Resistance Rs or
Rx
6
Ω
to 1000
Ω
to 4000
Ω
For Resistance transmitter:
Resistance range Rs of sliding contact
For Resistance/potentiometer:
Shifting resistance range Rx
Resistance Re
0 W to 4000
Ω
For Resistance transmitter:
Resistance Re between sliding contact
(S) and end (E), if the sliding contact is
positioned at the end.
Parameter
Selection/settings
Description
?
?
?
?
?
?
?
?