7 configuration – in setup program only, 1 customer-specific linearization, Configuration – in setup program only – JUMO 705020 mTRON T - Analog Input Module, 4-Ch. Operating Manual User Manual
Page 53: Customer-specific linearization
53
7 Configuration – in setup program only
7.1
Customer-specific linearization
You can use the customer-specific linearization to create a customized linearization character-
istic line for analog inputs. This characteristic line is used for all analog inputs for which the cor-
responding linearization has been selected in the configuration.
Customer-specific linearization can only be programmed with the setup program. Two proce-
dures are available for this (type of linearization: grid points or formula).
Signalfluss
TIP!
The parameters described in this section can only be configured with the setup program.
TIP!
It is possible to create different characteristic lines with grid points and formula. The relevant
point, however, is which kind of linearization is currently selected when the dialog box is
closed by clicking "OK". The corresponding characteristic line is then used in the module.
<<<<
>>>>
y
x
<<<<
>>>>
+
+
(1)
(2)
(3)
(4)
(5)
(6)
(7)
(1) Measured value
(5) Offset (standardized)
(2) Offset (physical)
(6) Linearized value monitoring with respect to
the scale (configuration parameter: Scale
start, Scale end)
(3) Measured value monitoring of standard sig-
nals (limits acc. to NAMUR)
(7) Linearized value
(4) Linearization (grid points / formula)
Grid points: Domain monitoring (measured
values)
Formula: Co-domain monitoring (linearized
values) with respect to the measuring range
(configuration parameter: Measuring range
start, Measuring range end)