beautypg.com

JULABO FC600-T Recirculating cooler User Manual

Page 9

background image

Recirculating coolers

9



(with T-pump)

FCW2500T

Working temperature range

°C -25 ... 80

Cooling capacity

°C +20 +10 +5 0 -10 -20

(water-glycol)

kW 2.5 2.0 1.8 1.5 0.8 0.25

Refrigerant

R404A

Heater capacity

kW 1.2

Pump capacity:
Pressure max.

bar 3.5

Flow rate max.

Lpm 28

Pump connections

M16x1

Noise level, 1 m distance

dBA 70

Filling volume

l 8 ... 11

Dimensions (WxLxH)

cm 46 x 61 x 49

Shipping weight

kg 74

Mains power connection

V/Hz 230/60

Total power consumption

W 2800




(with S-pump)

FC1200S

FCW1200S

Working temperature range

°C -15 ... 80 -15 ... 80

Cooling capacity

°C

20 10 5 -10

(water-glycol)

kW

0.12 0.85 0.65 0.26

Refrigerant

R134a

Heater capacity

kW

1.2

Pump capacity:
Pressure max.

bar

1.2

Flow rate max.

l/min

22 / 15

with tubing connections

mm dia.

13.5 / 9.5

Pump connections

M16x1

Noise level, 1 m distance

dBA 57

53

Filling volume

l

8 ... 11

Dimensions (WxLxH)

cm

46 x 61 x 49

Ambient temperature

°C

5 ... 40

Shipping weight

kg 66

68

Mains power connection

V/Hz

208-230/60 or 230/50

Total power consumption

W

2800


All data have been determined at

mains voltage: 230 V / 50 Hz

ambient temperature: 20 °C

bath liquid: water-glycol