JULABO FC600-T Recirculating cooler User Manual
Page 8

Operator responsibility – Safety instructions
8
2.4. Technical
specifications
(with T-pump)
FC1200T
FCW1200T
Working temperature range
°C
-10 ... 80
-10 ... 80
Cooling capacity
°C
20 10 -10
(water-glycol)
kW
0.11 0.75 0.15
Refrigerant
R134a
Heater capacity
kW
1.2
Pump capacity:
Pressure max.
bar
3.5
Flow rate max.
Lpm
28
Pump connections
M16x1
Noise level, 1 m distance
dBA 58
53
Filling volume
l
8 ... 11
Dimensions (WxLxH)
cm
46 x 61 x 49
Ambient temperature
°C
5 ... 40
Shipping weight
kg 67
69
Mains power connection
V/Hz
208-230/60 or 230/50
Total power consumption
W
2600
(with T-pump)
FC1600T
FCW1600T
Working temperature range
°C -15 ... 80
-15 ... 80
Cooling capacity
°C
20 10 -10
(water-glycol)
kW
1.45 1.05 0.25
Refrigerant
R134a
Heater capacity
kW
1.2
Pump capacity:
Pressure max.
bar
3.5
Flow rate max.
Lpm
28
with tubing connections
mm dia.
13.5 / 9.5
Pump connections
M16x1
Noise level, 1 m distance
dBA 58
53
Filling volume
l
8 ... 11
Dimensions (WxLxH)
cm
46 x 61 x 49
Ambient temperature
°C
5 ... 40
Shipping weight
kg 67
69
Mains power connection
V/Hz
208-230/60 or 230/50
Total power consumption
W
2700
All data have been determined at
rated voltage and frequency
ambient temperature: 20 °C
bath liquid: water-glycol
- FC1200-T Recirculating cooler FC1600-T Recirculating cooler FCW2500T Recirculating cooler FCW1600T Recirculating cooler FCW1200T Recirculating cooler FCW1600S Recirculating cooler FCW1200S Recirculating cooler FC1600T Recirculating cooler FC1200T Recirculating cooler FC1600S Recirculating cooler FC1200S Recirculating cooler