2.4. Technical

specifications

(with T-pump)

FC1200T

FCW1200T

Working temperature range

°C

-10 ... 80

-10 ... 80

Cooling capacity

°C

20 10 -10

(water-glycol)

kW

0.11 0.75 0.15

Refrigerant

R134a

Heater capacity

kW

1.2

Pump capacity:
Pressure max.

bar

3.5

Flow rate max.

Lpm

28

Pump connections

M16x1

Noise level, 1 m distance

dBA 58

53

Filling volume

l

8 ... 11

Dimensions (WxLxH)

cm

46 x 61 x 49

Ambient temperature

°C

5 ... 40

Shipping weight

kg 67

69

Mains power connection

V/Hz

208-230/60 or 230/50

Total power consumption

W

2600


(with T-pump)

FC1600T

FCW1600T

Working temperature range

°C -15 ... 80

-15 ... 80

Cooling capacity

°C

20 10 -10

(water-glycol)

kW

1.45 1.05 0.25

Refrigerant

R134a

Heater capacity

kW

1.2

Pump capacity:
Pressure max.

bar

3.5

Flow rate max.

Lpm

28

with tubing connections

mm dia.

13.5 / 9.5

Pump connections

M16x1

Noise level, 1 m distance

dBA 58

53

Filling volume

l

8 ... 11

Dimensions (WxLxH)

cm

46 x 61 x 49

Ambient temperature

°C

5 ... 40

Shipping weight

kg 67

69

Mains power connection

V/Hz

208-230/60 or 230/50

Total power consumption

W

2700


All data have been determined at

rated voltage and frequency

ambient temperature: 20 °C