beautypg.com

JULABO FC600-T Recirculating cooler User Manual

Page 10

background image

Operator responsibility – Safety instructions

10


(with S-pump)

FC1600S

FCW1600S

Working temperature range

°C -15 ... 80 -15 ... 80

Cooling capacity

°C

20 10 5 -10

(water-glycol)

kW

1.55 1.15 0.9 0.36

Refrigerant

R134a

Heater capacity

kW

1.2

Pump capacity:
Pressure max.

bar

1.2

Flow rate max.

l/min

22 / 15

with tubing connections

mm dia.

13.5 / 9.5

Pump connections

M16x1

Noise level, 1 m distance

dBA 57

53

Filling volume

l

8 ... 11

Dimensions (WxLxH)

cm

46 x 61 x 49

Ambient temperature

°C

5 ... 40

Shipping weight

kg 66

68

Mains power connection

V/Hz

208-230/60 or 230/50

Total power consumption

W

2900

(with Ju-pump)

FC600 -T

Working temperature range

°C -20 ... 80

Cooling capacity

°C 20 10 5 -10

(water-glycol)

kW 0.6 0.47 0.4 0.21

Refrigerant

R134a

Heater capacity

kW 1.2

Pump capacity:
Pressure max.

bar 0.5

Flow rate max.

Lpm 20 / 14

with tubing connections

mm dia 13,5/9,5

Pump connections

M16x1

Noise level, 1 m distance

dBA 51

Filling volume

l 6 ... 8

Dimensions (WxLxH)

cm 46 x 61 x 49

Ambient temperature

°C 5 ... 40

Shipping weight

kg 48

Mains power connection

V/Hz 208-230/60 or 230/50

Total power consumption

W 2000


All data have been determined at

rated voltage and frequency

ambient temperature: 20 °C

bath liquid: water-glycol