6 input heat transfer, 7 input trip point 1, 8 input trip point 2 – INFICON PSG55x ATM to Medium Vacuum Gauge (EtherCAT) User Manual
Page 19

tira85e1 (2013-06) PxG55x.cp
19
Is set if the device is not in Safe State (value (I 0x6nn0, SI 0x11) = valid)
TxPdoState
0
1
Invalid
Valid
The corrected, converted, calibrated final analog input value of the sensor.
Index
SI
DataType
NV Access PM Name
6023 0x01
BOOL RO tx
Reading
Valid
0x02
BOOL
RO
tx
Overrange
Exceeded
0x03
BOOL
RO
tx
Underrange
Exceeded
Indicates whether the Value parameter contains a valid value within the specified
accuracy or not.
Reading Valid
0 Invalid
1 Valid
Indicates whether the Value parameter contains a value in over range.
Reading Valid
0
No Overrange Exceeded
1 Overrange
Exceeded
Indicates whether the Value parameter contains a value in under range.
Reading Valid
0
No Underrange Exceeded
1 Underrange
Exceeded
Index
SI
DataType
NV Access PM Name
600E
0x01 BOOL
RO
tx
Status High Trip
0x02 BOOL
RO
tx
Status Low Trip
Status High Trip
0
1
High Trip not assert
High Trip assert
Status Low Trip
0
1
Low Trip not assert
Low Trip assert
Index
SI
DataType
NV Access PM Name
600F
0x01 BOOL
RO
tx
Status High Trip
0x02 BOOL
RO
tx
Status Low Trip
Subindex 0x0E
Subindex 0x11
4.4.6 Input Heat Transfer
Subindex 0x01
Subindex 0x02
Subindex 0x03
4.4.7 Input Trip Point 1
Subindex 0x01
Subindex 0x02
4.4.8 Input Trip Point 2