• PCG gauges with or without ATM: The "Manufacturer Configuration Module 1"

is assigned to the CDG module.

• PSG gauges: The "Manufacturer Configuration Module 1" is assigned to the

Pirani module.

Index

SI

DataType

NV Access PM Name

2800 0x01

BYTE RW Safe

State

0x02

REAL

RW

Safe

Value

Specifies the behavior for the value for States other than Valid.

Safe State

0
1
2
3

Zero
Full Scale
Hold last value
Use safe value

Safe Value: The value to be used for Safe State = Safe Value.

• PCG gauges with ATM: The "Manufacturer Configuration Module 2" is assigned

to the ATM module.

• PCG gauges without ATM: The "Manufacturer Configuration Module 2" is

assigned to the Pirani module.

Index

SI

DataType

NV Access PM Name

2801 0x01

BYTE RW Safe

State

0x02

REAL

RW

Safe

Value

Specifies the behavior for the Value for states other than Valid.

Safe State

0
1
2
3

Zero
Full Scale
Hold last value
Use safe value

Safe Value: The value to be used for Safe State = Safe Value.

• PCG gauges with ATM: The "Manufacturer Configuration Module 3" is assigned

to the Pirani module.

Index

SI

DataType

NV Access PM Name

2802 0x01

BYTE RW Safe

State

0x02

REAL

RW

Safe

Value

4.3.2 Manufacturer

Configuration Module 1

Subindex 0x01

Subindex 0x02

4.3.3 Manufacturer

Configuration Module 2
(PCG with or without
ATM only)

Subindex 0x01

Subindex 0x02

4.3.4 Manufacturer

Configuration Module 3
(PCG with ATM only)