HYDAC ENS 3000 User Manual
Page 14
![background image](/manuals/562192/14/background.png)
E
14
7.2
SUMMARY OF THE BASIC SETTINGS
Setting Display Settings
available
Default
setting
Assignment of switching output 1 (S.S.1)
Switching output 1 to switch
at the pre-set fluid level.
niv / TEMP niv
Switching output 1 to switch at the
pre-set temperature
Switching mode, switching output 1 (S.m.1)
Switching output 1 is operating in
switching point hysteresis mode
SP / Win
SP
Switching output 1 is operating in
window mode
Switching direction, switching output 1
(S.d.1)
Normally open.
ON / OFF ON
Normally closed.
Switch-on delay, switching output 1 (Ton 1)
Time, in seconds, which must elapse once the
switching point has been reached or exceeded
before a switching operation will occur.
Increment: 1s
0 .. 9999s 1
Switch-off delay, switching output 1 (Toff 1)
Time, in seconds, which must elapse once the
fluid level/temperature has fallen below the
particular switch-back point before a switching
operation will occur.
0 .. 9999s 1
Settings for switching output 2, 3 or 4 are made as above