7.2

SUMMARY OF THE BASIC SETTINGS

Setting Display Settings

available

Default
setting

Assignment of switching output 1 (S.S.1)

Switching output 1 to switch
at the pre-set fluid level.

niv / TEMP niv

Switching output 1 to switch at the
pre-set temperature

Switching mode, switching output 1 (S.m.1)

Switching output 1 is operating in
switching point hysteresis mode

SP / Win

SP

Switching output 1 is operating in
window mode

Switching direction, switching output 1
(S.d.1)

Normally open.

ON / OFF ON

Normally closed.

Switch-on delay, switching output 1 (Ton 1)

Time, in seconds, which must elapse once the
switching point has been reached or exceeded
before a switching operation will occur.
Increment: 1s

0 .. 9999s 1

Switch-off delay, switching output 1 (Toff 1)

Time, in seconds, which must elapse once the
fluid level/temperature has fallen below the
particular switch-back point before a switching
operation will occur.

0 .. 9999s 1

Settings for switching output 2, 3 or 4 are made as above