beautypg.com

Dip 2 - “af, Dip 3 - “hsr 240v, Dip 4 - “esr 230v – ETC CEM3 v1.5.1 User Manual

Page 47: Dip 5 - “nd, Dips 6-8, Termination switches, N o t e

background image

3

Common Tasks

41

DIP 2 - “AF”

This switch should be set to “On” if your rack has Advanced Features (AF - see

Advanced

Features (AF), page 10

).

DIP 3 - “HSR 240V”

This switch should be set to “On” if your rack is an HSR rack intended for use with 240VAC

power feeds.

DIP 4 - “ESR 230V”

This switch should be set to “On” if your rack is an ESR rack intended for use with 230VAC

power feeds.

DIP 5 - “ND”

This switch should be set to “On” if your rack includes a neutral disconnect.

DIPs 6-8

These DIP switches are used together to determine the number of module slots in your

rack. Refer to the table below to find the desired settings for your rack size.

Termination Switches

DMX signal requires a a signal termination at the end of a data run. If your rack is the last

device on the data run for either DMX A or DMX B, set the termination switch for the

appropriate run to “ON”. The switches are labeled “B” or “A” on the backplane label.

If the rack is not the last device on either data run, leave these set to “Off”.

N o t e :

For JSR dimmer racks, intended for use with 100VAC power feeds, both DIP 3

and DIP 4 should be set to “On”.

DIP Number

Rack size

6

7

8

6 module slots

Off

On

On

12 module slots

Off

On

Off

24 module slots

Off

Off

On

36 module slots

On

Off

Off

48 module slots

Off

Off

Off