CiDRA SONARtrac HD GVF-100 User Manual
Page 85
Copyright © 2006 CiDRA Corporation
Page 10-7
20675-02 Rev 01
‘Low Cutoff’ - Setting at which the Pulse output will turn off.
Care must be taken to configure the multiplier and pulse width to allow
the full range of the pulse output to be:
1. Measurable by the user’s equipment. There may be a limitation
on the minimum pulse width the user’s equipment can detect.
2. Less than the maximum pulses per second allowed by the
transmitter.
The maximum number of pulses per second that can be output is
based on the selected Pulse Width (see table below):
Max Pulses = 500/Pulse Width
Table 15
Maximum Pulse Per Second Based On Pulse Width
‘Output Sel’ - Used to select the measurement to be output.
The Info>Configuration>Pulse Output selection on the transmitter
menu displays the currently configured max/min pulse range, and will
indicate an over range condition if one exists (i.e. settings exceed
maximum pulses per second capability).
Pulse Width
Pulse Per Second
Maximum
0.5 ms
1000
1.0 ms
500
20 ms
25
33 ms
15.15
50 ms
10
100 ms
5
Warning: Settings Produce > Max PPS!