CiDRA SONARtrac HD GVF-100 User Manual
Page 71

Copyright © 2006 CiDRA Corporation
Page 9-18
20675-02 Rev 01
Table 14 Transmitter Menu Tree Software Release 03.03.XX (page 3)
Level 1
Level 2
Level 3
Range
Description
Output Sel
Flow Rate, SOS, GVF,
Blank
Parameter to output
Power Sel
Internal, External
Power supply for 4-
20mA current
Low End
Based on ‘output sel’
Low end output (4mA)
High End
Based on ‘output sel’
High end output (20mA)
Out of Range
Hold, >20mA, <4mA,
4mA
Behavior when meter
reading is out of range
or meter has no reading
Overrange
Rail
Enable, Disable
‘Enable’ causes the
output to go to full
(20mA) or min (4mA)
when system over
ranges
4mA Trim
2 to 6
Adjust 4mA output
4-20mA
Ch1& Ch2
20mA Trim
18 to 22
Adjust 20mA output
Multiplier
0 - 999999
Multiplier on output
Width (ms)
.5,1,20,33,50,100
Pulse width
Lowcut
0 % to 100 %
Low end cutoff
Pulse
Output Sel
Flow Rate, Totalizer,
Flow Rate%, GVF, SOS
Parameter to output
Warning Off/On
Activates alarm warning
function
Critical
0 % to 100 % Off/On
Activates alarm critical
function
Alarm
Control
Manual Clear Off/On
Allows for manual or
automatic alarm
clearing
Flw Min
Flw Max
GVF Min
Alarm
Warning
Threshold
GVF Max
0-100% of range
Used to set the
minimum and maximum
values for a warning
alarm
Flw Min
Flw Max
GVF Min
Output Config
Alarm Critical
Threshold
GVF Max
0-100% of range
Used to set the
minimum and maximum
values for a critical
alarm
Table 14 Transmitter Menu Tree Software Release 03.03.XX (page 4)