Udp application: multi-point pair connection – Atop Technology SE5001A User manual User Manual
Page 44
User Manual Version 1.0
SE5001A Serial Device Server
42
3.3.16. UDP Application: Multi-Point Pair Connection
It is also possible to setup pair connection in UDP mode to have more than one Pair Connection Master or Slave to
communicate to each other. For example, it is possible to setup one Modbus Master and six Modbus Slaves in UDP
(Figure 3.31). Note again that UDP does not guarantee data delivery and only data would be transmitted over
Ethernet; other serial pings are not transmitted. If RS-232 along with flow control, it is recommended to use
Multi-Point Pair Connection in TCP (section
).
Note that the Destination IP and Port of the Slaves need to be equal to the Master’s IP and Port. Local
Listening Port of the Slaves needs to be equal to the Master’s Destination Port.
Sample Configuration:
IP Address
Link Mode
Local Listening Port
Destination IP
Destination Port
SE5001A Master
10.0.50.100
UDP
5000
10.0.50.200~10.0.50.207
5000
SE5001A Slave 1
10.0.50.200
UDP
5000
10.0.50.100
5000
SE5001A Slave 2
10.0.50.201
UDP
5000
10.0.50.100
5000
SE5001A Slave 3
10.0.50.202
UDP
5000
10.0.50.100
5000
SE5001A Slave 4
10.0.50.203
UDP
5000
10.0.50.100
5000
SE5001A Slave 5
10.0.50.204
UDP
5000
10.0.50.100
5000
SE5001A Slave 6
10.0.50.205
UDP
5000
10.0.50.100
5000
Figure 3.31 Multi-Point UDP Pair Connection with Modbus