Transmitter for level measurement, Trouble shooting – WIKA 732.15.100 User Manual
Page 12
12
11592011.04 06/2014 GB/D/F/I
GB
WIKA operating instructions differential pressure gauge models 712.15.100, 732.15.100
Defect
Possible reason
Remedy
No signal output
Failure of power supply
Check power supply and wiring
Wiring interrupted (or broken)
replace defective components
Transmitter incorrectly wired
Check wiring;
if necessary rectify it
No pressure
Check tailpipes
Open press. compensation valve
Close pressure compensation valve
Electronic defect e.g. through
Return pressure gauge to
incorrect supply voltage
manufacturer for repair
or stray voltage spikes
Steady signal
Pressure entry blocked
Check tailpipes and pressure entry
despite pressure
bore, if necessary clean it carefully
variation
Open press. compensation valve Close pressure compensation valve
Electronic defect e.g. through
Return pressure gauge to
incorrect supply voltage
manufacturer for repair
or stray voltage spikes
Transmitter defect after being
Return pressure gauge to
over-pressured
manufacturer for repair
Steady and too high
Electronic defect through
Return pressure gauge to
signal despite of
incorrect supply voltage
manufacturer for repair
pressure variation
or stray voltage spikes
Full span reading too low Supply voltage too low
Adjust supply voltage
Load impedance too high
Consider permissible max. load
Wrong scale selected
Check position of scale selection
switch
Zero signal too low
Wrong zero compensation
Readjust zero point
Zero signal too high
Wrong zero compensation
Readjust zero point
Transmitter over-pressured
Return pressure gauge to
manufacturer for repair
8. Transmitter for level measurement
Trouble shooting