beautypg.com

Discharge piping checklist, Bypass-piping considerations, Auxiliary-piping checklist – Goulds Pumps 3610 - IOM User Manual

Page 31

background image

Installation

Check

Explanation/comment

Checked

Make sure that the suction piping

This prevents air from entering the

is adequately submerged below

pump through a suction vortex.

the surface of the liquid source.

Discharge piping checklist

Checklist

Check

Explanation/comment

Checked

Check that an isolation valve is in-

The isolation valve is required for:

stalled in the discharge line.

• Priming
• Regulation of flow
• Inspection and maintenance of the pump

Check that a check valve is installed in The location between the isolation valve and the
the discharge line, between the isola-

pump allows inspection of the check valve.

tion valve and the pump discharge

The check valve prevents damage to the pump and

outlet.

seal due to the back flow through the pump, when
the drive unit is shut off. It is also used to restrain
the liquid flow.

If increasers are used, check that they
are installed between the pump and
the check valve.
If quick-closing valves are installed in

This protects the pump from surges and water

the system, check that cushioning de- hammer.
vices are used.

Bypass-piping considerations

When to use a bypass line

Provide a bypass line for systems that require operation at reduced flows for prolonged
periods. Connect a bypass line from the discharge side (before any valves) to the source of
suction.

When to install a minimum-flow orifice

You can size and install a minimum-flow orifice in a bypass line in order to prevent bypassing
excessive flows. Consult your ITT representative for assistance in sizing a minimum-flow
orifice.

When a minimum-flow orifice is unavailable

Consider an automatic recirculation control valve or solenoid-operated valve if a constant
bypass (minimum-flow orifice) is not possible.

Auxiliary-piping checklist

Precautions

WARNING:

• Cooling systems such as those for bearing lubrication and mechanical-seal systems must be

operating properly to prevent excess heat generation, sparks, and premature failure.

• Sealing systems that are not self-purging or self-venting, such as plan 23, require manual venting

prior to operation. Failure to do so will result in excess heat generation and seal failure.

NOTICE:
The mechanical seal must have an appropriate seal-flush system. Otherwise, excess heat
generation and seal failure can occur.

Installation, Operation, and Maintenance Manual

29