Other Displays:
Open probe detection is standard on all Pitco 
controls. If probe is detected open, normal 
heating and cooking activities are suspended. 
This display warns operators that the vat 
temperature has exceeded set temperature by 
+40°F (+22°C), or an absolute maximum of 410°F 
(210°C). The alarm will also sound. This display 
does not show the status of the mechanical high 
limit switch. 
This message indicates that the drain valve has 
been opened, the vat is assumed to be empty by 
the controller. Normal heat control activities are 
suspended. Display will show an alternating 
message [DRAINING] [TURN OFF]. To restore to 
normal operation, close the drain value. Display 
will show [TURN OFF] [TURN OFF]. 
Turn controller off, and refill the vat. Continue 
with normal operations at section 1. 
This message indicates that the heating system 
failed to respond. Typically, the high temperature 
limit switch has tripped and is in need of resetting. 
In the case on gas fired appliances, this message 
will display if the pilot fails to light or is detected 
marginal by the ignition module. 
This message indicates a shorted probe. If probe 
is detected as a short circuit, normal heating and 
cooking activities are suspended. 
This message indicates the computer has lost 
communication with the autofilter control board 
and oil management operations are suspended. 
Normal cooking activities are unaffected. 