Horner APG SmartBlock HE-579ACM300 User Manual
Page 5

MAN0951-02
12 May 2011
PAGE 5
HE-579ACM300
Information is subject to change without notice.
Consumed Analog Data – This data is sent from the controller to the SmartBlock. For typical
applications the I/O configuration setup in Cscape will automatically populate this data. For more
advanced applications you may use NetPut functions to write this data. Please see the advanced
programming guide MAN0880 for more details.
Word
Description
Details
Word 1 / 2
REAL
PT A Ratio
Word 3 / 4
REAL
PT B Ratio
Word 5 / 6
REAL
PT C Ratio
Voltage Input Ratio
For example 120 to 480 step up enter 0.25
for 7200 to 480 step down enter 15
Word 7 / 8
REAL
CT A Ratio
Word 9 / 10
REAL
CT B Ratio
Word 11 / 12
REAL
CT C Ratio
Current Input Ratio
For example for 5A:100A CT enter 20
Word 13 / 14
REAL
CT A Phase Shift
Word 15 / 16
REAL
CT B Phase Shift
Word 17 / 18
REAL
CT C Phase Shift
Phase correction for CTs Enter in degrees
Min of -1.63° Lag, Max of +3.32 Lead
Word 19 / 20
REAL
Zero Cross Timeout
Seconds for zero cross alarm – max 2.5
Word 21 / 22
REAL
RMS Sag Voltage Level Voltage Sag level in volts
Word 23
UINT
Sag Half Cycles
Number of half cycles before alarm
Word 24
UINT
Peak Level Half Cycles
Number of half cycles before alarm
Word 25 / 26
REAL
Voltage Peak Level
Voltage level for peak alarm
Word 27 / 28
REAL
Current Peak Level
Current level for peak alarm
Produced Analog Data – This data is sent from the SmartBlock to the controller. Normally this data is
mapped into specific registers in the I/O configuration in Cscape. For advanced applications NetGet
functions can be used to obtain this data. Since this data is broadcast to all controllers on the network
additional controllers can use NetGet functions to obtain this data as well.
Word
Function
Word 1 / 2
REAL
Phase A RMS Voltage
Word 3 / 4
REAL
Phase B RMS Voltage
Word 5 / 6
REAL
Phase C RMS Voltage
Word 7 / 8
REAL
Phase A RMS Current
Word 9 / 10
REAL
Phase B RMS Current
Word 11 / 12
REAL
Phase C RMS Current
Word 13 / 14
REAL
Frequency
Word 15 / 16
REAL
Watts
Word 17 / 18
REAL
PF Power Factor
Word 19 / 20
REAL
VA Volt-Amps
Word 21 / 22
REAL
VAR Volt-Amps Reactive
Word 23 / 24
REAL
KWhr
Word 25 / 26
REAL
Voltage Peak
Word 27 / 28
REAL
Current Peak