Horner APG QX751 OCS User Manual
Page 4
MAN0889-03-EN
Specifications / Installation
__________________________________________________________________________________________________________________________________________________
11/20/2009 Page 4
of 6 1023
Figure 6 – Port 3 (CN1) RS-485 Port
3.3.3
DIP-Switch
The DIP switch is used for setting the terminating resistance of the RS-485 signal line at the CN1, MJ1, or MJ2 connector.
Figure 7 – DIP Switch
(1)
Set DIPSW 8 to ON position when termination is required on MJ2.
(2)
Set DIPSW 7 at the terminating station of the QX751 units to the ON position when connecting PLCs through RS-422/485.
(3)
Set DIPSW 6 to ON position when termination is required on MJ1.
(4)
Set DIPSW 5 to the ON position to add a terminating signal to SD when connecting through RS-422/485.
(5)
DIPSW 1, 2, 3 and 4 are for future use, keep these in OFF position.
Shielded Cable
Send Data (-)
To RS-485 Port
SG
Send Data (+)
Receive Data (-)
Receive Data (+)
SG
7
-SD
13
Port 3
+SD
12
-RD
25
+RD
24
FG
1
Signal Pin No.
Shielded Cable
Receive Data
SG
SG
Send Data
To RS-232 Port
SG
7
CS
5
Port 3
RS
4
RD
3
SD
2
FG
1
Signal Pin No.
Figure 5 – Port 3 (CN1) RS-232 Port