Specifications / Installation

XLE103-10


5

Analog Conditioning

5.1

Filter

Filter Constant sets the level of digital filtering according to the following
chart.















Digital Filtering.

The illustration above demonstrates the effect of digital

filtering (set with Filter Constant) on module response to a
temperature change.

It is recommended that the filter constant for the HE-XE103-10 be set to a
value of 7. This will minimize noise and jitter, improve effective resolution,
and provide adequate speed for most temperature monitor and control
applications.

5.2

Thermistor Linearization


Thermistors are measured using a half-bridge circuit that exhibits variable resolution
and the associated increased measurement range.

Temperature, degrees C

Resolution, degrees C

-55

1.05

-35

0.36

-15

0.17

5

0.11

25

0.1

45

0.13

65

0.22

85

0.30

105

0.55

125

0.85

145

1.35


Best resolution is at 25°C, 77°F. With a constant 0.1°C resolution circuit, the
measurement range would only extend from –26°C to + 76°C.

Linearization must be performed by the user in the ladder application code, using 26
internal %R registers per channel. The example below uses %R1-26 to linearize one
channel - %AI1. Linearization consists of the following example steps.

1. Load the desired linearization coefficients into a table on First Scan using a Move
Constant Data block.


Registers (Real)

Degrees C

Degrees F

R0011

-1.94454e-028

-3.50017e-028

R0013

2.40268e-023

4.32483e-023

R0015

-1.24101e-018

-2.23381e-018

R0017

3.46655e-014

6.23979e-014

R0019

-5.69403e-010

-1.02493e-009

R0021

5.62368e-006

1.01226e-005

R0023

-0.0353121

-0.0635617

R0025

163.878

326.981

2. Load %AI0001 into %R0001 as a Real.

3. Perform the Real Math Expression
%R3 = (((%R11*%R1+%R13)*%R1+%R15)*%R1+%R17)

4. Perform the Real Math Expression %R5 =
(((%R3*%R1+%R19)*%R1+%R21)*%R1+%R23)*%R1+%R25

5. Load %R0005 result into another register such as %R0007 to save the temperature
value.

Steps 2 though 5 can be on a single rung.

The expression rung may be copied, substituting %AI0002 and %R00011 for %AI0001 and
%R0007, and used to linearize the second channel. Contact Horner APG for an example file
containing the above program.

5.3

Thermistor types

The HE-XE103-10 with the given example ladder code supports Kele Engineering Precon
Type III, 10 K

thermistors. It also directly supports the following 10 K

(Beta=3574)

thermistors from Yellow Springs Instruments (YSI).


44006 46006
44106 46031
44406 46041
44031 44907
45006 44908


6

I/O Register Map

Registers

Description

%I1 to %I24

Digital Inputs

%I32

Output Fault

%I25 to %I31

Reserved

%Q1 to %Q16

Digital outputs

%Q17

Clear HSC1 accumulator to 0

%Q18

Totalizer: Clear HSC2

Quadrature 1-2: Accumulator 1

Reset to max – 1

%Q19

Clear HSC3 Accumulator to 0

%Q20

Totalizer: Clear HSC4

Quadrature 3-4: Accumulator 3

Reset to max – 1

%Q21 to %Q32

Reserved

%AI1 to %AI4

Analog inputs

%AI5, %AI6

HSC1 Accumulator

%AI7, %AI8

HSC2 Accumulator

%AI9, %AI10

HSC3 Accumulator

%AI11, %AI12

HSC4 Accumulator

%AQ1, %AQ2

PWM1 Duty Cycle

%AQ3, %AQ4

PWM2 Duty Cycle

%AQ5, %AQ6

PWM Prescale

%AQ7, %AQ8

PWM Period

%AQ9 to %AQ14

Analog outputs

Note: Not all XLe units contain the I/O listed in this table.


Registers

PWM

HSC

Stepper

%AQ1

Start

Frequency

%AQ2

PWM1 Duty

Cycle

(32 bit)

HSC1

Preset

Value

Run

Frequency

%AQ3

%AQ4

PWM2 Duty

Cycle

(32 bit)

HSC2

Preset

Value

Accel Count

(32 bit)

%AQ5
%AQ6

PWM Prescale

(32 bit)

Run Count

(32 bit)

%AQ7
%AQ8

PWM Period

(32 bit)

Decel Count

(32 bit)

%Q1

Run

%I30

Ready/Done

%I31

Error










60

20

100

40

80

20

0

10

100

90
80
70
60
50
40
30

Scans

0

1

2

3

4

5

6

0

7

%

C

o

m

p

le

te

[

]

Filter
Constant