AMETEK 2110 Shut Height Monitor User Manual
Page 55
Installation and Programming Manual
50
Appendix A: Error Messages
51
Installation and Programming Manual
Appendix A: Error Messages
The following charts contain descriptions and solutions for the three types of errors that can appear
on the monitor’s LED display. To clear errors, perform the solutions found in charts A-1, A-2, and
A-3, followed by pressing either the scroll, shift, or enter.
Chart A-1 System Errors
Chart A-2 Operating Errors
Error Displayed
Error Description
Solution
SEr101
A configuration error has occurred.
Contact GEMCO Tech. Support.
SEr102
The monitor's function parameter
memory has been corrupted.
Contact GEMCO Tech. Support.
SEr103
The battery for the monitor's memo-
ry is low.
Contact GEMCO Tech. Support.
SEr104
A software fault has occurred.
Contact GEMCO Tech. Support.
SEr105
An error has occurred with the
monitor's internal memory locations.
Clear the error and contact GEMCO
Tech. Support.
SEr106
A firmware CRC error has occurred. Contact GEMCO Tech. Support.
SEr320
This is a resolver-specific error. See
Chart A-6.
SEr330
The input device is not connected to
the monitor's input module.
Connect the input device to the
input module and clear the error.
SEr331
This is an LDT-specific error. See
Chart A-7.
Error Displayed
Error Description
Solution
OEr101
The press's ram did not move within
the time programmed in the Move
Detection Time-Out function.
Review press operation and/or in-
crease the value of the Move Detec-
tion Time-Out function.
OER330 or
OEr320
The press's shut height moved be-
yond the value programmed in the
Negative Over Travel Limit Func-
tion.
Review press operation and/or
increase the value of the negative
Over Travel Limit function.
T13692 appendix a.indd
3/17/04, 6:54 AM
51