Chapter 4: Programming
47
Installation and Programming Manual
Chapter 4: Programming
8. Select function key.
9. Enter function number X03. Select enter key.
The monitor displays current maximum positions value.
10. Enter 2000. Select enter key. This sets maximum position value at 2000
counts.
The monitor displays 002000.
11. Select Function key.
The monitor displays “F-----”.
12. Enter function number X06. Select enter key.
The monitor displays current voltage output value linked to maximum count
value.
14. Enter 8. Select enter key. This sets a maximum voltage output value of
8VDC at 2000 counts or more.
The monitor displays 008000.
Analog output channel 2 is programmed using the same basic sequences except with the
function numbers noted below. Remember that the X shown in the function number represents
the slot in which the analog output board is installed in the Interface Module chassis.
Analog Output Channel 2 - Function numbers
A)
Select voltage or current output
Function No. X10
B)
Scaling analog output
- Select minimum position
Function No. X08
- Select analog output value to be linked to minimum position value
Function No. X11
Analog output channel 1 will now provide a 2 to 8 VDC output as position increases between
500 and 2000 counts. Position values below 500 will result in a 2 VDC analog output. Position
values above 2000 will result in an 8 VDC output.