Adjust the Turns Counting Factor
20. Select the function key.
The monitor displays “F-----”.
21. Select function number 301 (Turns Counting function). Select the enter key.
The monitor displays “001000”.
22. Enter 001000. Select the enter key.
23. Select the function key.
The monitor displays “F-----”.
24. Select function number 302 (Position Offset function). Select the enter key.
The monitor displays the current position of the shut height.
25. Enter the actual position of the shut height as measured from the bed to the
ram. It is recommended that a set of inside micrometers be used to acquire
this information.
To verify that you have accurately calibrated the resolver, move the slide
adjust 1.000”. After this has been done, the new position indicated should
also have moved 1.000”.
After configuring the resolver to the shut height monitor, you can proceed to
Section 4.3: Monitor Setup functions.
301
Enter
001000
Enter
000000
302
There are two input cards available for use with LDTs.
1. Specified as option V1 in the part number and is labeled (FMIP01) on the card.
2. Specified as option L1 in the part number and is labeled (FMIP02) on the card.
The configuration of the module and this LDT is different depending on which module you have
ordered. Determine which module you have and proceed to the section below for programming
instructions.
4.2: LDT Configuration Functions
(F)
8
8
(F)
8
8