beautypg.com

A specifications, Power requirements, Space requirements – HP Netserver L Server series User Manual

Page 113

background image

105

A Specifications

Power Requirements

Table A-1. Power Requirements

Voltage and frequency

200-240 VAC; 47-63Hz.

Maximum continuous power
input

1560W

Maximum inrush current

80A for 10 ms

Delayed action circuit breaker
recommended

208/240 60hz: NEMA AB1 20A
220/230/240 50hz -- IEC MCB 16A, type C (single
server per rack) or type D (multiple servers per rack).

Power availability

200W continuous to PCI cards and internal drives

NOTE

The HP NetServer LXr Pro8 includes a total of four power
supplies. The system requires three functional supplies at all
times; individual supplies can be hot-swapped.

Space Requirements

Table A-2. Space Requirements

System dimensions

17.5 in. high x 19.0 in wide x 32.1 in deep

(44.5 cm high x 48.6 cm wide x 81.53 cm deep)

Rack space

10 EIA units

Rack clearance

46 in. (117 cm) beyond rear of HP rack (door mounted)
30 in. (76 cm) beyond rear of HP rack (no door)

System weight

170 lb. (76 kg)