beautypg.com

A site power cables, Required documentation, Requirements for site power or ground cables – HP Integrity BL870c Server-Blade User Manual

Page 46

background image

A Site Power Cables

Site cables and lugs must be provided by the customer or the installation provider for the customer.
HP does not provide these items to the customer.

IMPORTANT:

The power cables should be assembled by a certified electrician only.

Required Documentation

The information in this appendix assumes the customer or the customer’s installation provider is
already familiar with and has access to the National Fire Protection Associations (NFPAs) published
National Electrical Code Handbook 2005 (NFPA 70). Specifically either of these tables from the
handbook, depending on the environment at the site (60C-90C vs. 150C-250C jacketing):

“Allowable Ampacities of Insulated Conductors Rated 0 Through 2000 Volts, 60° C Through
90° C, Not More Than Three Current-Carrying Conductors in Raceway, Cable, or Earth,
Based on Ambient Temperature of 30° C” (Table 310.16)

“Allowable Ampacities of Insulated Conductors Rated 0 Through 2000 Volts, 150° C Through
250° C (302° F Through 482° F). Not More Than Three Current-Carrying Conductors in
Raceway, Cable, or Earth, Based on Ambient Temperature of 40° C (104° F)” (Table 310.18)

Requirements for Site Power or Ground Cables

The customer must ensure the site power cables meet the ampacity requirements for a NEBS 50°C
environment.

CAUTION:

Use Table 310.16 or Table 310.18 along with Table 310.15(B)(2)(a) (see

“Required

Documentation” (page 46)

) to verify the site power input cables meet the ampacity requirements

for a NEBS 50°C environment.

To ensure the site power input cables you plan to use meet the ampacity requirements for a NEBS
50°C environment:

Depending on the site’s Cable Rating requirements, use Table 310.16 or Table 310.18
(60C-90C or 150C-250C jacketing, respectively) (see

“Required Documentation” (page 46)

)

to determine the correct cable size, based on the type and grade of cable that you plan to
use.

To reach the NEBS 50°C environment, apply the correction factor within each table for the
50°C ambient temperature range (Table 310.16 is 46C-50C; Table 310.18 is 41C-50C) to
the ampacity values in the Table to obtain the corrected maximum ampacity that is acceptable
in the NEBS 50°C environment.

If more than three current-carrying conductors will be run vertically through the sides of the
cabinet, or lay in a site’s raceway for longer than 24 inches, apply the correction factor from
Table 310.15(B)(2)(a) to the ampacity values from Table 310.16 or Table 310.18 at 50°C.

46

Site Power Cables