beautypg.com

3 specifications, Environmental specifications, Seismic rack specifications – HP Integrity BL870c Server-Blade User Manual

Page 15: Floor space requirements, Chapter 3

background image

3 Specifications

Environmental Specifications

Value

Specification

Temperature range

1

-5 to 50 ºC ambient temperature

Operating

-40 to 70 ºC

Non operating

Relative humidity (non-condensing)

2

5 to 90% relative humidity

Operating

5 to 93% relative humidity

Non operating

Altitude

Operating

40 ºC from sea level to 6,000 ft.
30 ºC from 6,000 ft. to 13,000 ft.

Earthquake Zone 4

Seismic resistance

1

Temperature ratings are shown for sea level. No direct sunlight allowed.

2

Storage maximum humidity of 93% is based on a maximum temperature of 40°C.

Seismic Rack Specifications

Value

Specification

36U

U Height

26.7 in (67.8 cm)

Width

1

39.4 in (100.0 cm)

Depth

Top, Bottom

Cable Entry

1200 lbs (544.3 kg)

Max Load

500 lbs (226.8 kg)
485 lbs (219.9 kg) - R2 rack

Rack Weight

200 lbs (90.7 kg)

Packaging and Pallet Weight

1

Including side panels.

Floor Space Requirements

Recommended

Minimum

Measurement

cm

in

cm

in

130

51.2

91.4

36

Front (appearance side) clearance

130

51.2

91.4

36

Rear (service side) clearance

< 2.5

< 1.0

--

--

Space between cabinets

68.6

27

--

--

Cabinet pitch

Environmental Specifications

15