3 specifications, Environmental specifications, Seismic rack specifications – HP Integrity BL870c Server-Blade User Manual
Page 15: Floor space requirements, Chapter 3
3 Specifications
Environmental Specifications
Value
Specification
Temperature range
1
-5 to 50 ºC ambient temperature
Operating
-40 to 70 ºC
Non operating
Relative humidity (non-condensing)
2
5 to 90% relative humidity
Operating
5 to 93% relative humidity
Non operating
Altitude
Operating
40 ºC from sea level to 6,000 ft.
30 ºC from 6,000 ft. to 13,000 ft.
Earthquake Zone 4
Seismic resistance
1
Temperature ratings are shown for sea level. No direct sunlight allowed.
2
Storage maximum humidity of 93% is based on a maximum temperature of 40°C.
Seismic Rack Specifications
Value
Specification
36U
U Height
26.7 in (67.8 cm)
Width
1
39.4 in (100.0 cm)
Depth
Top, Bottom
Cable Entry
1200 lbs (544.3 kg)
Max Load
500 lbs (226.8 kg)
485 lbs (219.9 kg) - R2 rack
Rack Weight
200 lbs (90.7 kg)
Packaging and Pallet Weight
1
Including side panels.
Floor Space Requirements
Recommended
Minimum
Measurement
cm
in
cm
in
130
51.2
91.4
36
Front (appearance side) clearance
130
51.2
91.4
36
Rear (service side) clearance
< 2.5
< 1.0
--
--
Space between cabinets
68.6
27
--
--
Cabinet pitch
Environmental Specifications
15