17.
CONVERT C TO F
INPUT 1:
A
PROMPT:
DVxx INPUT
°
C
ACTUATOR:
n/a
RESET:
n/a
OUTPUT:
= (A * 9/5) +32
18.
BTU
INPUT 1:
F
PROMPT:
DVxx FLOW
INPUT 2:
TEMPH
PROMPT:
DVxx HIGHER TEMP
INPUT 3:
TEMPL
PROMPT:
DVxx LOWER TEMP
INPUT 4:
C
PROMPT:
DVxx SCALING CONST.
ACTUATOR:
n/a
RESET:
n/a
OUTPUT:
= C*F* (TEMPH-TEMPL)
If INPUT 4 is "NOT USED", then C=1
NOTES:
F - Flow
TEMPH - Higher Temperature for DeltaT
TEMPL - Lower Temperature for DeltaT
C - Scaling Constant
The Temperatures can be degrees F or C, but the scaling constant must take this into
account.
19.
ADD
INPUT 1:
A
PROMPT:
DVxx INPUT 1
INPUT 2:
B
PROMPT:
DVxx INPUT 2
INPUT 3:
C
PROMPT:
DVxx INPUT 3
INPUT 4:
D
PROMPT:
DVxx INPUT 4
ACTUATOR:
n/a
RESET:
n/a
OUTPUT:
= A+B+C+D
20.
AVG
INPUT 1:
A
PROMPT:
DVxx INPUT 1
INPUT 2:
B
PROMPT:
DVxx INPUT 2
INPUT 3:
C
PROMPT:
DVxx INPUT 3
INPUT 4:
D
PROMPT:
DVxx INPUT 4
ACTUATOR:
n/a
RESET:
n/a
OUTPUT:
= (A+B+C+D)/E
Where E is the number of inputs that are CONFIGURED.