Snmp issues, 6103 lvvxhv, Snmp – APC Network Management Card none User Manual
Page 65: Troubleshooting, Management card frqwlqxhg

Network Management Card User’s Guide
58
SNMP issues
The following table describes known
SNMP
problems.
3UREOHP
6ROXWLRQ
Unable to perform a GET
• Verify the read (GET) community name.
• Use the Control Console or Web Interface to ensure
that the
NMS
has access. See
Unable to perform a SET
• Verify the read/write (SET) community name.
• Use the Control Console or Web Interface to ensure
that the
NMS
has write (SET) access. See
Unable to receive traps at
the NMS
Query the
mconfigTrapReceiverTable
PowerNet
MIB
OID
to see if the
NMS
IP
address is listed correctly, and
the community name defined for the
NMS
matches the
community name in the table. If not, use SETs to the
mconfigTrapReceiverTable
OID
s, or use the Control
Console or Web Interface to correct the trap receiver
definition problem. See
Traps received at an
NMS
are not identified
See your
NMS
documentation to verify that the traps
are properly integrated in the alarm/trap database.