36

Device Manager Menus

UPS Configuration

FRQWLQXHG

Shutdown
Parameters

All of the following settings are available with Smart-UPS, Matrix-UPS,
Symmetra, and Symmetra 3 Phase UPS models. The

Shutdown

Behavior Settings

for a Silcon DP300E series UPS uses only the

Low-

Battery Duration

,

Maximum Shutdown TIme

, and

Shutdown Delay

settings.

Note:

In the Control Console, you use the

Battery

option in the

Configuration

menu to access the

Return Battery Capacity

setting.

&RQWLQXHG RQ QH[W SDJH

6HWWLQJ

'HILQLWLRQ

Return Battery
Capacity

Defines the minimum battery capacity that must be present
before the

UPS

turns on after a shutdown that was caused by a

power failure.

Note:

The

UPS

must also wait until the time defined by the

Return Delay

setting expires before it can turn on.

Low-Battery
Duration

Defines how the

UPS

can continue to run on battery once a low-

battery condition occurs.

Note:

This setting also defines how much time PowerChute

has to safely shut down its server in response to the

Turn UPS Off Gracefully

,

Reboot Gracefully

, and

Put

UPS To Sleep Gracefully

Control

menu options.

Maximum
Shutdown Time
(Web Interface
only)

Reports the maximum time that the UPS will wait before it shuts
down in response to graceful turn-off command, as defined by
the

Maximum Shutdown TIme

setting for the PowerChute

®

option

.

Note

: For information about how the

Maximum Shutdown

TIme

is determined, see

Maximum-Shutdown-Time

negotiation on page 40

.

Shutdown Delay

Defines how long the

UPS

will wait before it shuts down in

response to a turn-off command.

Return Delay

Defines how long a

UPS

must wait before it turns on after a

shutdown that was caused by a power failure.

Note:

The

UPS

must also have the capacity specified by the

Return Battery Capacity

setting before it can turn on.

Sleep Time

Defines how long the

UPS

will sleep (stay turned off) when you

use either one of the

Control

menu’s sleep options (

Put UPS To

Sleep

or

Put UPS To Sleep Gracefully

).

Note:

This setting also appears in the “Control” page.